CVE-2025-39205Medium 6.5A vulnerability exists in the IEC 61850 in MicroSCADA X SYS600 product. The certificate validation of the TLS protocol allows remote Man-in-the-Middle attack due to missing proper validation.0.2%
CVE-2025-39204Medium 6.5A vulnerability exists in the Web interface of the MicroSCADA X SYS600 product. The filtering query in the Web interface can be malformed, so returning data can leak unauthorized information to the us0.4%
CVE-2025-39203Medium 6.5A vulnerability exists in the IEC 61850 of the MicroSCADA X SYS600 product. An IEC 61850-8 crafted message content from IED or remote system can cause a denial of service resulting in disconnection lo0.2%
CVE-2025-39202High 7.3A vulnerability exists in in the Monitor Pro interface of the MicroSCADA X SYS600 product. An authenticated user with low privileges can see and overwrite files causing information leak and data corru0.2%
CVE-2025-39201Medium 6.1A vulnerability exists in MicroSCADA X SYS600 product. If exploited this could allow a local unauthenticated attacker to tamper a system file, making denial of Notify service.0.1%
CVE-2024-3980Critical 9.9The MicroSCADA Pro/X SYS600 product allows an authenticated user input to control or influence paths or file names
that are used in filesystem operations. If exploited the vulnerability allows the att0.6%
CVE-2024-4872Critical 9.9A vulnerability exists in the query validation of the MicroSCADA Pro/X SYS600 product. If exploited this could allow an authenticated attacker to inject code towards persistent data. Note that to succ0.5%
CVE-2022-3353Medium 5.9IEC 61850 MMS-Server Vulnerability in multiple Hitachi Energy Products1.1%
CVE-2022-29492Medium 5.3A vulnerability exists in the handling of a malformed IEC 104 TCP packet. Upon receiving a malformed IEC 104 TCP packet, the malformed packet is dropped, however the TCP connection is left open. This may cause a denial-of-service if the affected conne ...0.7%
CVE-2022-1778High 7.5A vulnerability exists during the start of the affected SYS600, where an input validation flaw causes a buffer-overflow while reading a specific configuration file. Subsequently SYS600 will fail to start. The configuration file can only be accessed by ...0.5%
CVE-2022-29922High 7.5A vulnerability exists in the handling of a specially crafted IEC 61850 packet with a valid data item but with incorrect data type in the IEC 61850 OPC Server. The vulnerability may cause a denial-of-service on the IEC 61850 OPC Server part of the SYS ...0.8%
CVE-2022-2277High 7.5A vulnerability exists in the ICCP stack of the affected SYS600 versions due to validation flaw in the process that establishes the ICCP communication. The validation flaw will cause a denial-of-service when ICCP of SYS600 is request to forward any da ...0.8%
CVE-2022-29490High 8.5A vulnerability exists in the Workplace X WebUI in which an authenticated user is able to execute any MicroSCADA internal scripts irrespective of the authenticated user's role.0.7%