Vulnerability · Published Sep 14, 2022 · Assigned by Hitachi Energy

CVE-2022-29922A vulnerability exists in the handling of a specially crafted IEC 61850 packet with a valid data item but with incorrect data type in the IEC 61850 OPC Server. The vulnerability may cause a denial-of-service on the IEC 61850 OPC Server part of the SYS ...

High 7.5

In plain English

A high-severity improper input validation in MicroSCADA Pro SYS600 from Hitachi Energy. There are no confirmed reports of exploitation so far. The chance it is exploited in the next 30 days is estimated at 0.8% (higher than 56% of all known vulnerabilities).

Severity (CVSS 3.1)7.5High
Exploit odds (30 days)0.8%top 43.5% of all CVEs
Exploited in the wildNo reportsCISA SSVC: none
Attack toolingNoneno public tooling known

Official description

Improper Input Validation vulnerability in the handling of a specially crafted IEC 61850 packet with a valid data item but with incorrect data type in the IEC 61850 OPC Server in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. The vulnerability may cause a denial-of-service on the IEC 61850 OPC Server part of the SYS600 product. This issue affects: Hitachi Energy MicroSCADA Pro SYS600 version 9.4 FP2 Hotfix 4 and earlier versions Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.4:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:*

Affected products (as reported)

VendorProductVersions
Hitachi Energy MicroSCADA X SYS600 1010.110.1.110.210.2.110.310.3.1
Hitachi Energy MicroSCADA Pro SYS600 unspecified – through 9.2 FP2 Hotfix 4

Weakness: CWE-20 · Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

References