Vulnerability · Published Sep 14, 2022 · Assigned by Hitachi Energy
CVE-2022-2277A vulnerability exists in the ICCP stack of the affected SYS600 versions due to validation flaw in the process that establishes the ICCP communication. The validation flaw will cause a denial-of-service when ICCP of SYS600 is request to forward any da ...
High 7.5
In plain English
A high-severity security flaw in MicroSCADA X SYS600 from Hitachi Energy. There are no confirmed reports of exploitation so far. The chance it is exploited in the next 30 days is estimated at 0.8% (higher than 56% of all known vulnerabilities).
Official description
Improper Input Validation vulnerability exists in the Hitachi Energy MicroSCADA X SYS600's ICCP stack during the ICCP communication establishment causes a denial-of-service when ICCP of SYS600 is request to forward any data item updates with timestamps too distant in the future to any remote ICCP system. By default, ICCP is not configured and not enabled. This issue affects: Hitachi Energy MicroSCADA X SYS600 version 10.2 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:*
Affected products (as reported)
| Vendor | Product | Versions |
|---|---|---|
| Hitachi Energy | MicroSCADA X SYS600 | 10.210.2.110.310.3.1 |
Weakness: CWE-1284 · Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H