Vulnerability · Published Aug 12, 2025 · Assigned by siemens

CVE-2025-40570

Low 2.4

In plain English

A low-severity resource allocation without limits in SIPROTEC 5 6MD84 (CP300) from Siemens. There are no confirmed reports of exploitation so far. The chance it is exploited in the next 30 days is estimated at 0.2% (higher than 12% of all known vulnerabilities).

Severity (CVSS 3.1)2.4Low
Exploit odds (30 days)0.2%top 88.0% of all CVEs
Exploited in the wildNo reportsCISA SSVC: none
Attack toolingNoneno public tooling known

Official description

A vulnerability has been identified in SIPROTEC 5 6MD84 (CP300) (All versions < V10.0), SIPROTEC 5 6MD85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 6MD86 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 6MD89 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 6MU85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7KE85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SA82 (CP150) (All versions < V10.0), SIPROTEC 5 7SA86 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SA87 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SD82 (CP150) (All versions < V10.0), SIPROTEC 5 7SD86 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SD87 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SJ81 (CP150) (All versions < V10.0), SIPROTEC 5 7SJ82 (CP150) (All versions < V10.0), SIPROTEC 5 7SJ85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SJ86 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SK82 (CP150) (All versions < V10.0), SIPROTEC 5 7SK85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SL82 (CP150) (All versions < V10.0), SIPROTEC 5 7SL86 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SL87 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SS85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7ST85 (CP300) (All versions < V10.0), SIPROTEC 5 7ST86 (CP300) (All versions < V10.0), SIPROTEC 5 7SX82 (CP150) (All versions < V10.0), SIPROTEC 5 7SX85 (CP300) (All versions < V10.0), SIPROTEC 5 7SY82 (CP150) (All versions < V10.0), SIPROTEC 5 7UM85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7UT82 (CP150) (All versions < V10.0), SIPROTEC 5 7UT85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7UT86 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7UT87 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7VE85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7VK87 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7VU85 (CP300) (All versions < V10.0), SIPROTEC 5 Compact 7SX800 (CP050) (All versions < V10.0). Affected devices do not properly limit the bandwidth for incoming network packets over their local USB port. This could allow an attacker with physical access to send specially crafted packets with high bandwidth to the affected devices thus forcing them to exhaust their memory and stop responding to any network traffic via the local USB port. Affected devices reset themselves automatically after a successful attack. The protection function is not affected of this vulnerability.

Affected products (as reported)

VendorProductVersions
Siemens SIPROTEC 5 6MD84 (CP300) 0 – before V10.0
Siemens SIPROTEC 5 6MD85 (CP300) V7.80 – before V10.0
Siemens SIPROTEC 5 6MD86 (CP300) V7.80 – before V10.0
Siemens SIPROTEC 5 6MD89 (CP300) V7.80 – before V10.0
Siemens SIPROTEC 5 6MU85 (CP300) V7.80 – before V10.0
Siemens SIPROTEC 5 7KE85 (CP300) V7.80 – before V10.0
Siemens SIPROTEC 5 7SA82 (CP150) 0 – before V10.0
Siemens SIPROTEC 5 7SA86 (CP300) V7.80 – before V10.0
Siemens SIPROTEC 5 7SA87 (CP300) V7.80 – before V10.0
Siemens SIPROTEC 5 7SD82 (CP150) 0 – before V10.0
Siemens SIPROTEC 5 7SD86 (CP300) V7.80 – before V10.0
Siemens SIPROTEC 5 7SD87 (CP300) V7.80 – before V10.0
Siemens SIPROTEC 5 7SJ81 (CP150) 0 – before V10.0
Siemens SIPROTEC 5 7SJ82 (CP150) 0 – before V10.0
Siemens SIPROTEC 5 7SJ85 (CP300) V7.80 – before V10.0
Siemens SIPROTEC 5 7SJ86 (CP300) V7.80 – before V10.0
Siemens SIPROTEC 5 7SK82 (CP150) 0 – before V10.0
Siemens SIPROTEC 5 7SK85 (CP300) V7.80 – before V10.0
Siemens SIPROTEC 5 7SL82 (CP150) 0 – before V10.0
Siemens SIPROTEC 5 7SL86 (CP300) V7.80 – before V10.0
Siemens SIPROTEC 5 7SL87 (CP300) V7.80 – before V10.0
Siemens SIPROTEC 5 7SS85 (CP300) V7.80 – before V10.0
Siemens SIPROTEC 5 7ST85 (CP300) 0 – before V10.0
Siemens SIPROTEC 5 7ST86 (CP300) 0 – before V10.0
Siemens SIPROTEC 5 7SX82 (CP150) 0 – before V10.0
Siemens SIPROTEC 5 7SX85 (CP300) 0 – before V10.0
Siemens SIPROTEC 5 7SY82 (CP150) 0 – before V10.0
Siemens SIPROTEC 5 7UM85 (CP300) V7.80 – before V10.0
Siemens SIPROTEC 5 7UT82 (CP150) 0 – before V10.0
Siemens SIPROTEC 5 7UT85 (CP300) V7.80 – before V10.0

Weakness: CWE-770 · Vector: CVSS:3.1/AV:P/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L