Vulnerability · Published May 3, 2024 · Assigned by zdi
CVE-2023-39468Triangle MicroWorks SCADA Data Gateway DbasSectorFileToExecuteOnReset Exposed Dangerous Function Remote Code Execution Vulnerability
High 7.2
In plain English
A high-severity security flaw in SCADA Data Gateway from Triangle MicroWorks. There are no confirmed reports of exploitation so far. The chance it is exploited in the next 30 days is estimated at 1.9% (higher than 80% of all known vulnerabilities).
Official description
Triangle MicroWorks SCADA Data Gateway DbasSectorFileToExecuteOnReset Exposed Dangerous Function Remote Code Execution Vulnerability. This vulnerability allows remote attackers to execute arbitrary code on affected installations of Triangle MicroWorks SCADA Data Gateway. Authentication is required to exploit this vulnerability. The specific flaw exists within the handling of DbasSectorFileToExecuteOnReset parameter. The issue results from an exposed dangerous function. An attacker can leverage this vulnerability to execute code in the context of SYSTEM. Was ZDI-CAN-20799.
Affected products (as reported)
| Vendor | Product | Versions |
|---|---|---|
| Triangle MicroWorks | SCADA Data Gateway | 5.1.3.20324 |
Weakness: CWE-749 · Vector: CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H
References
- ZDI-23-1036 x_research-advisory
- vendor-provided URL vendor-advisory