Vulnerability · Published Oct 31, 2022 · Assigned by icscert
CVE-2022-41629
High 7.5
In plain English
A high-severity missing authentication in InfraSuite Device Master from Delta Electronics. There are no confirmed reports of exploitation so far. The chance it is exploited in the next 30 days is estimated at 0.7% (higher than 55% of all known vulnerabilities).
Official description
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior allow unauthenticated users to access the aprunning endpoint, which could allow an attacker to retrieve any file from the “RunningConfigs” directory. The attacker could then view and modify configuration files such as UserListInfo.xml, which would allow them to see existing administrative passwords.
Affected products (as reported)
| Vendor | Product | Versions |
|---|---|---|
| Delta Electronics | InfraSuite Device Master | 0 – through 00.00.01a |
Weakness: CWE-306 · Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N
References
- https://www.cisa.gov/uscert/ics/advisories/icsa-22-298-07 government-resource