Vulnerability · Published Sep 14, 2021 · Assigned by siemens

CVE-2021-33737

High 7.5

In plain English

A high-severity memory corruption in SIMATIC CP 343-1 Advanced (incl. SIPLUS variants) from Siemens. There are no confirmed reports of exploitation so far. The chance it is exploited in the next 30 days is estimated at 1.1% (higher than 65% of all known vulnerabilities).

Severity (CVSS 3.1)7.5High
Exploit odds (30 days)1.1%top 35.4% of all CVEs
Exploited in the wildNo reportsnot in CISA KEV
Attack toolingNoneno public tooling known

Official description

A vulnerability has been identified in SIMATIC CP 343-1 (incl. SIPLUS variants) (All versions), SIMATIC CP 343-1 Advanced (incl. SIPLUS variants) (All versions), SIMATIC CP 343-1 ERPC (All versions), SIMATIC CP 343-1 Lean (incl. SIPLUS variants) (All versions), SIMATIC CP 443-1 (All versions < V3.3), SIMATIC CP 443-1 (All versions < V3.3), SIMATIC CP 443-1 Advanced (All versions < V3.3), SIPLUS NET CP 443-1 (All versions < V3.3), SIPLUS NET CP 443-1 Advanced (All versions < V3.3). Sending a specially crafted packet to port 102/tcp of an affected device could cause a denial of service condition. A restart is needed to restore normal operations.

Affected products (as reported)

Weakness: CWE-119 · Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:U/RC:C