Vulnerability · Published Mar 12, 2026 · Assigned by icscert

CVE-2026-3611Honeywell IQ4x BMS Controller Missing authentication for critical function

Critical 10.0

In plain English

A critical-severity missing authentication in IQ3 from Honeywell. There are no confirmed reports of exploitation so far. The chance it is exploited in the next 30 days is estimated at 5.7% (higher than 93% of all known vulnerabilities). Ready-made attack tooling exists: public proof-of-concept code.

Severity (CVSS 3.1)10.0Critical
Exploit odds (30 days)5.7%top 6.9% of all CVEs
Exploited in the wildNo reportsCISA SSVC: none
Attack tooling1Public PoC

Official description

The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.

Affected products (as reported)

VendorProductVersions
Honeywell IQ4E v3.50_3.44 – through 4.36 (build 4.3.7.9)
Honeywell IQ412 v3.50_3.44 – through 4.36 (build 4.3.7.9)
Honeywell IQ422 v3.50_3.44 – through 4.36 (build 4.3.7.9)
Honeywell IQ4NC v3.50_3.44 – through 4.36 (build 4.3.7.9)
Honeywell IQ41x v3.50_3.44 – through 4.36 (build 4.3.7.9)
Honeywell IQ3 v3.50_3.44 – through 4.36 (build 4.3.7.9)
Honeywell IQECO v3.50_3.44 – through 4.36 (build 4.3.7.9)

Weakness: CWE-306 · Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H

References