Vulnerability · Published Oct 10, 2023 · Assigned by siemens
CVE-2023-36380
Critical 9.8
In plain English
A critical-severity hard-coded credentials in CP-8031 MASTER MODULE from Siemens. There are no confirmed reports of exploitation so far. The chance it is exploited in the next 30 days is estimated at 0.4% (higher than 35% of all known vulnerabilities).
Official description
A vulnerability has been identified in CP-8031 MASTER MODULE (All versions < CPCI85 V05.11 (only with activated debug support)), CP-8050 MASTER MODULE (All versions < CPCI85 V05.11 (only with activated debug support)). The affected devices contain a hard-coded ID in the SSH `authorized_keys` configuration file. An attacker with knowledge of the corresponding private key could login to the device via SSH. Only devices with activated debug support are affected.
Affected products (as reported)
| Vendor | Product | Versions |
|---|---|---|
| Siemens | CP-8031 MASTER MODULE | All versions < CPCI85 V05.11 (only with activated debug support) |
| Siemens | CP-8050 MASTER MODULE | All versions < CPCI85 V05.11 (only with activated debug support) |
Weakness: CWE-798 · Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C