Vulnerability · Published Oct 31, 2022 · Assigned by icscert
CVE-2022-40202
Critical 9.8
In plain English
A critical-severity missing authentication in InfraSuite Device Master from Delta Electronics. There are no confirmed reports of exploitation so far. The chance it is exploited in the next 30 days is estimated at 1.6% (higher than 76% of all known vulnerabilities).
Official description
The database backup function in Delta Electronics InfraSuite Device Master Versions 00.00.01a and prior lacks proper authentication. An attacker could provide malicious serialized objects which, when deserialized, could activate an opcode for a backup scheduling function without authentication. This function allows the user to designate all function arguments and the file to be executed. This could allow the attacker to start any new process and achieve remote code execution.
Affected products (as reported)
| Vendor | Product | Versions |
|---|---|---|
| Delta Electronics | InfraSuite Device Master | 0 – through 00.00.01a |
Weakness: CWE-306 · Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
References
- https://www.cisa.gov/uscert/ics/advisories/icsa-22-298-07 government-resource