Vulnerability · Published Jan 11, 2022 · Assigned by siemens
CVE-2021-45033
High 8.8
In plain English
A high-severity hard-coded credentials in CP-8000 MASTER MODULE WITH I/O -25/+70°C from Siemens. There are no confirmed reports of exploitation so far. The chance it is exploited in the next 30 days is estimated at 0.9% (higher than 61% of all known vulnerabilities).
Official description
A vulnerability has been identified in CP-8000 MASTER MODULE WITH I/O -25/+70°C (All versions < V16.20), CP-8000 MASTER MODULE WITH I/O -40/+70°C (All versions < V16.20), CP-8021 MASTER MODULE (All versions < V16.20), CP-8022 MASTER MODULE WITH GPRS (All versions < V16.20). An undocumented debug port uses hard-coded default credentials. If this port is enabled by a privileged user, an attacker aware of the credentials could access an administrative debug shell on the affected device.
Affected products (as reported)
| Vendor | Product | Versions |
|---|---|---|
| Siemens | CP-8000 MASTER MODULE WITH I/O -25/+70°C | All versions < V16.20 |
| Siemens | CP-8000 MASTER MODULE WITH I/O -40/+70°C | All versions < V16.20 |
| Siemens | CP-8021 MASTER MODULE | All versions < V16.20 |
| Siemens | CP-8022 MASTER MODULE WITH GPRS | All versions < V16.20 |
Weakness: CWE-798
References
- https://cert-portal.siemens.com/productcert/pdf/ssa-324998.pdf x_refsource_MISC