Vulnerability · Published Sep 14, 2021 · Assigned by siemens
CVE-2021-27391
Critical 9.8
In plain English
A critical-severity buffer overflow in APOGEE MBC (PPC) (P2 Ethernet) from Siemens. There are no confirmed reports of exploitation so far. The chance it is exploited in the next 30 days is estimated at 3.4% (higher than 89% of all known vulnerabilities).
Official description
A vulnerability has been identified in APOGEE MBC (PPC) (P2 Ethernet) (All versions >= V2.6.3), APOGEE MEC (PPC) (P2 Ethernet) (All versions >= V2.6.3), APOGEE PXC Compact (BACnet) (All versions < V3.5.3), APOGEE PXC Compact (P2 Ethernet) (All versions >= V2.8), APOGEE PXC Modular (BACnet) (All versions < V3.5.3), APOGEE PXC Modular (P2 Ethernet) (All versions >= V2.8), TALON TC Compact (BACnet) (All versions < V3.5.3), TALON TC Modular (BACnet) (All versions < V3.5.3). The web server of affected devices lacks proper bounds checking when parsing the Host parameter in HTTP requests, which could lead to a buffer overflow. An unauthenticated remote attacker could exploit this vulnerability to execute arbitrary code on the device with root privileges.
Affected products (as reported)
| Vendor | Product | Versions |
|---|---|---|
| Siemens | APOGEE MBC (PPC) (P2 Ethernet) | All versions >= V2.6.3 |
| Siemens | APOGEE MEC (PPC) (P2 Ethernet) | All versions >= V2.6.3 |
| Siemens | APOGEE PXC Compact (BACnet) | All versions < V3.5.3 |
| Siemens | APOGEE PXC Compact (P2 Ethernet) | All versions >= V2.8 |
| Siemens | APOGEE PXC Modular (BACnet) | All versions < V3.5.3 |
| Siemens | APOGEE PXC Modular (P2 Ethernet) | All versions >= V2.8 |
| Siemens | TALON TC Compact (BACnet) | All versions < V3.5.3 |
| Siemens | TALON TC Modular (BACnet) | All versions < V3.5.3 |
Weakness: CWE-120 · Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
References
- https://cert-portal.siemens.com/productcert/pdf/ssa-944498.pdf x_refsource_MISC